MLC 8000 Link Converter MOSCAD NFM I/O Monitoring Indications (Non IP Simulcast)
Legend:
- EXS = Existence or presence
- L2V = Link to VGU (From AGU)
- L2B = Link to one or more BRs
- RST = Restart
- <xxxxxxxxxxx> are the first eleven (11) characters uniquely identifying the specific MLC 8000 unit (as configured in the SDM3000 Builder project)
- Severity:
- critical – a problem that affects the entire channel
- major – one site of the channel is affected at both reception and transmission
- minor – one site of the channel is affected in one direction (the transmit direction)
- normal – report of status (only when the user performs the restart from GMC Application)
Note
- Name and Description are limited to 15 characters.
- On and Off messages are limited to 15 characters.
Pin |
|
SDM3000 Builder | |||||||
---|---|---|---|---|---|---|---|---|---|
# | Name | I/O | Object | Name | "On" Message | "Off" Message | Description | Legend | Severity |
1 | 5v | Output | AI | EXS-xxxxxxxxxxx | Present | Not Present or VIP cable is disconnected | EXS-xxxxxxxxxxx | Unit presence | major |
3 | VIP2 | N/A | N/A | Not used | |||||
4 | VIP3 | Output | DI | L2V-xxxxxxxxxxx | VGU links fail | VGU link(s) OK | L2V-xxxxxxxxxxx | Cmprtr lnk fail | major |
5 | VIP4 | Output | DI | L2B-xxxxxxxxxxx | BR links failed | BR link(s) OK | L2B-xxxxxxxxxxx | Link to BR fail | major |
6 | VIP5 | N/A | N/A | Not used | |||||
7 | VIP6 | Input | DO | RST-xxxxxxxxxxx | Device restart | RST complete | RST-xxxxxxxxxxx | Restart device | normal |